Applies To:
  • CitectSCADA 5.42A, 5.50A

Summary:
A problem can occur when certain sequences of Cicode functions are used before calling the function TrnSetTime with an historical time. The function TrnSetTime, with an historical time, can fail to move a trend into historical mode. 

Solution:
Citect has confirmed this to be a problem in CitectHMI/SCADA versions v5.31 to v5.50. This problem has been fixed in version 5.50 Service Pack A. 

Keywords:
 

Attachments