Applies To: |
|
Summary: |
I have a DDE client that is logging String
tags that can sometimes have NULL string entries.
This results in the spurious error of the form 04/05/04-18:40:09 StrLengthCopy: invalid
parameters or copy truncated pDest=03A79130 being appended to the debug.log |
Solution: |
Citect has confirmed this to be a problem in CitectHMI/SCADA versions v5.42 to v5.50 Spk A. This problem has been fixed in version 6. |
Keywords: |
Related Links