Applies To:
  • CitectSCADA 5.xx
  • CitectHMI 5.xx

Summary:
Page opening times are very large when a large number of genies are on the page.  

Solution:
The slow page opening can be resolved by setting the INI parameter

[CTDRAW.general]
ComparePropertyLists=0 (default)

If the INI is set to 1 then you will open the page slowly, this can be useful

if you are experiencing issues where base genie property removal is not

propagating to nested genies

Citect has confirmed this to be a problem in CitectHMI/SCADA versions 5.41 Spk B to 5.50 Spk B. This problem has been fixed in version 6.

 

Keywords:
Genie Update Page Properties  