Applies To: |
|
Summary: |
A bit in my PLC that is set to 0 or 1 is appearing incorrectly in CitectSCADA (i.e. a 0 appears as a 1 or a 1 appears as a 0). |
Solution: |
This can be avoided by changing the PLC
project to utilise UDTs for digitals so that they are not being
aliased on a base tag (which is what has caused the problem).
Citect has confirmed this to be a problem in CitectHMI/SCADA ABCLX driver version v3.01.00.023. This will be resolved in the next major release of the driver. This has been resolved in v3.01.03.003 of the driver. |
Keywords: |
0, 1, ABCLX |
Related Links
Attachments