Applies To: |
|
Summary: |
I am using CitectSCADA version 6. When I use TrnAddHistory() to attach pre version 6 trend history files it returns a successful 0 but I cannot see anything in my trend display. |
Solution: |
The header format of trend data files has
changed slightly in version 6, where the log name field has
increased in length.
Citect has confirmed this to be a problem in CitectHMI/SCADA
version 6 and v6 SPK A. This has been resolved in CitectSCADA
v6.1. |