Applies To:
  • CitectSCADA 6.00
  • CitectHMI 6.00

I have developed my page templates in XGA (1024x768) resolution, but when I run my project on a SXGA (1280x1024) resolution screen, it does not fill the entire screen. I have set in my Citect.ini [page]dynamicsizing=1 and [animator]fullscreen=1. How do I resolve this issue? 

The best solution is to edit your page templates, and convert them to SXGA resolution. Then perform an update pages through the Graphics Builder. This may take some time, and may not suit all customers. A new feature has been introduced in CitectSCADA Version 6.0 which allows you to resize your window without maintaining the aspect ratio (Anisotropic resizing). By default this behaviour is switched off, but can be enabled by setting in your Citect.ini [page]MaintainAspectRatio=0.