Applies To:
  • CitectSCADA 5.xx, 6.00
  • CitectHMI 5.xx, 6.00

Summary:
I am using Multimonitors but my two Citect screens appear over the top of each other instead of one screen appearing on each monitor. 

Solution:
Many Multimonitors issues mainfest themselves by having one screen over the other screen on the first monitor. You are encouraged to read the Multimonitors guide that is available through Citect Support for a thorough explanation of how to correctly implement Multimonitors.

However, it has been noted that if the [Multimonitors]Screenwidth parameter does not match the screen resolution of the first screen, one screen will appear over the other.

Example:

[Multimonitors]
ScreenWidth=x

where x is the screen resolution of the first screen

 

Keywords:
 

Attachments