Citect will compile with an empty address
field for an ABCLX device tag. However, once the ABCLX device
starts up, a Citect GPF is generated and Citect runtime is
terminated. |
Solution: |
The workaround for this issue is to ensure
that a legitimate address is entered in the address for each and
every tag in your Citect project. Citect has confirmed this to be a problem in CitectHMI/SCADA version 5.41to 6.00. We are researching this problem and will post new information here as it becomes available. |
Keywords: |
ABCLX, crash, null, address |