Applies To:
  • CitectSCADA 5.41, 5.41 Service Pack A, 5.41 Service Pack B, 5.42, 5.42 Service Pack A, 5.50, 5.50 Service Pack A, 5.50 Service Pack B, 5.50 Service Pack C, 6.00
  • CitectHMI 5.41, 5.41 Service Pack A, 5.41 Service Pack B, 5.42, 5.42 Service Pack A, 5.50, 5.50 Service Pack A, 5.50 Service Pack B, 5.50 Service Pack C, 6.00

Summary:
Citect will compile with an empty address field for an ABCLX device tag. However, once the ABCLX device starts up, a Citect GPF is generated and Citect runtime is terminated.
 

Solution:
The workaround for this issue is to ensure that a legitimate address is entered in the address for each and every tag in your Citect project.

Citect has confirmed this to be a problem in CitectHMI/SCADA version 5.41to 6.00. We are researching this problem and will post new information here as it becomes available.
 

Keywords:
ABCLX, crash, null, address 
 