There is a work around to this problem.
You can create another instance of the Modnet driver. And thus
use whatever Modnet protocol parameters you wish for each instance
of the driver. Here are the instructions on how to do it:
1. Edit Protdir.dbf file.
Add the following line directly under the Modnet entry (insert new
line):
MODNETX MODNETX 1920 1920 0x37f
Note: You cannot use numeric numbers for the new MODNET instance
name, only alphabet characters.
2. Edit the ProtErr.dbf file.
Add the following line directly under the Modnet entry (insert new
line):
1 MODNETX Alias
Also these lines further down:
MODNETX 0 0x001C Bad response from PLC
MODNETX 0 0x100 Mismatch Gateway Point-To-Point
MODNETX 0 0x2100 Function code mismatch in reply
MODNETX 0 0x2101 Invalid BCD number
MODNETX 0 28 Bad response from PLC
3. Edit the Help.dbf file.
Add the following line directly after the Modnet entry:
PROTOCOL MODNETX
You should use the save_dbf.xls macro to save and close each of
these files to avoid corruption.
4. Now copy and rename modnet.dll and modnet.dbf to
modnetx.dll and modnetx.dbf.
5. Pack and compile your project.
6. You must create a unique port for each I/O Device that
uses each driver. For instance, Port1 for Modnet protocol. And
Port2 for Modnetx protocol.
7. You can now set the protdir.dbf BIT_BLOCK and MAX_LENGTH
parameters for each protocol. I.e. one set of parameters for
Modnet, and one for Modnetx.
8. You can also now use the Modnet protocol parameters in
the Citect.ini. I.e. you can use [Modnet]Block=250 and
[Modnetx]Block=5.
Citect will actually load 2 instances of essentially the same
driver.
Again note that you must have a unique port for each Driver
instance, otherwise you will get an error on startup from
Citect.
You can check in the Kernel under Units, that each protocol is
loaded with the appropriate parameters.
NOTE: This workaround solution is no longer suitable for
drivers that have been built since the start of 2007. However,
should you require a second instance of a particular Citect driver,
you can request that Citect rebuild a second instance for you.
Please contact Citect Support for further information.
Further to this most MODNET ini parameters
can be set on a per port basis.
|