What are the different settings I can use
for each of my ABCLX devices? |
Solution: |
In addition to the general ABCLX section
in the ini file (where parameters will effect all ABCLX devices on
the system), it is possible to configure the following ini
parameters on a per device basis (Please note: the values shown
below are default values): [<IOServer name>.<Port name>] FailOnBadData=1 ForwardOpenPoolSize=4 InactiveScanAdjust=10 DirectReadRefresh=500 MissedPollTolerance=3 LogTagInfo=0 LogTagInfoPath="C:\" For further information, please refer to the ABCLX help file Section "Advanced configuration and maintenance > Customizing a project using Citect.ini parameters" or contact Citect Support. |