If you attempt to read or write data from
more than one I/O device of the same remote multi-drop network by
forcing a connection using IODeviceControl() type 7, the second I/O
device connection attempt will fail because the remote modem is
engaged with the first I/O device connection. CitectSCADA will
attempt to connect with the remote modem if there is currently an
available dial-out modem on the I/O server. |
Solution: |
Citect has confirmed this to be a problem
in CitectHMI/SCADA versions 5.40 to 5.41 Spk B. This problem has
been fixed in version 5.42. |