Applies To: |
|
Summary: |
Client requests for data may fail to be
satisfied out of the I/O server cache due to differences in the way
the compiler and the I/O server block data requests. This problem can be obviated by disabling compiler blocking for remote I/O devices using the new citect.ini parameter; [GENERAL] DisableRemoteBlocking=1. |
Solution: |
Citect has confirmed this to be a problem
in CitectHMI/SCADA versions 5.20 to 5.41 Spk B. This problem has
been fixed in version 5.42. |
Keywords: |
Related Links