Applies To:
  • CitectSCADA 6.00
  • CitectHMI 6.00

Super Genie popup trends, do not display the trends configured. i.e. Data may be returned in the first instance of opening the super genie, however returning blank or N/A on other attempts. The problem seems to be more common with citect clients.

The problem occurs due to the reason that the popup page needs to be initialised before the assignments are made. Thus there needs to be a break between the time when the popup page is initialised, and the assigning of the Pens to the popup trend page. Sleep() function could be used, before assigning pens.

Missing Trends, Super Genie, Popup Trends