The order in which I/O devices are
configured has been reported to cause different problems. How
should I configure my I/O devices to avoid such issues? |
Solution: |
Citect has confirmed this to be a problem
in CitectHMI/SCADA version 5.50 SP B to v6.0. To avoid the issues,
Citect Support suggests that you setup your units.dbf in the
following way: IOServer1 PLC1 Primary IOServer1 PLC2 Primary IOServer2 PLC3 Primary IOServer2 PLC4 Primary IOServer2 PLC1_S Standby IOServer2 PLC2_S Standby IOServer1 PLC3_S Standby IOServer1 PLC4_S Standby Please be aware that not ordering your devices can result in the following: * Devices will come online, but no data is visible on the page * Communication is very slow We are researching this problem and will post new information here as it becomes available. |