Applies To: |
|
Summary: |
When multiple trends are exported using
TrnExportCSV, only the first trend is validated and if it is
invalid the whole sample is discarded regardless of whether the
other trends in the sample are valid or not. |
Solution: |
Citect has confirmed this to be a problem
in Citect for Windows versions up to 5.41. This problem has been
fixed in version 5.42. |