Applies To: |
|
Summary: |
Supergenies with a LONG datatype
association will generate hardware alarm: "cicode general value is
out of range" if you try and write to the variable a value greater
than 10,000,000. |
Solution: |
The workaround is to add the required
scaling ranges, raw and engineering, to the variable tags. Or if
this is too hard then you can set [CODE]ScaleCheck=0 in your
citect.ini parameter. |
Keywords: |
Supergenie, cicode general value is out of range, scales, [CODE]scalecheck |