Applies To: |
|
Summary: |
I can use the Unit Control Tag to put a
Control Recipe in HELD state, but I how can I pause/restart a batch
from the PLC after an error condition has passed? |
Solution: |
The new Batch API allows the Status of a
Control Recipe to be changed. The latest version of Batch_Example
(with Citect V6) shows how to do this. The example involves
releasing Control Recipes. Before restarting, set the Unit Control
Tag to 0 again using API function (ControlCR() in BatchAPIDemo
project can be used). If the Unit Control Tag Value is still 1 or 2
and you restart, the Unit will still be held. Prior to the Batch API you would need to restart using the Batch Scheduler. |
Keywords: |