The OPC driver can cause CitectSCADA to
hang under the following conditions: 1. A write request is issued to the driver 2. Processing the write operation takes a long time (such as the device being disconnected from the network and the operation needing to time out) 3. A read request is issued. CitectSCADA can hang processing the read request until the write request has finished processing. |
Solution: |
This problem has been fixed in OPC driver
version 1.11.11.1. |
Keywords: |
OPC disconnect hang pause offline |