Applies To: |
|
Summary: |
If an OPC device is defined with more than
32766 variable tags assigned to it then the OPC driver will not
subscribe to all the tags correctly. When CitectSCADA starts the I/O server will report that the unit has come online successfully. If any read requests are sent to the device it will report Unit Offline. The I/O server will then bring the unit online again and the process repeats. |
Solution: |
It is unwise to create a single OPC device
with this number of variable tags, if nothing else the device is
likely to take a very long time to come online due to the time it
takes to subscribe to each tag. In this situation it is recommended to create multiple I/O devices that all address the same OPC server. Each of these devices should have less than 32767 tags defined against them. This article supersedes Q3400. |
Keywords: |
OPC unit offline hardware alarm |
Related Links
Attachments