Unable to get communications to ABB Commander 351 |
Solution: |
Upon further testing it is found that a
limit of 8 consecutive analog registers can be read on one page and
only 32 consecutive digital registers can be read on one page. NOTE
: All tags works fine when only one tag is on a page 8 consecutive floating point addresses were used to read the analog values needed. PV (pH Tx) PV R REAL 416385 SP (pH) SP (read only) R REAL 416387 SPW SP (write only) W (A or M) INT 40120 OP (FCV) OP1 R/(W in MAN) REAL 416389 OPW OP1 W (in MAN) INT 40022 AI2 (Flow Tx) R REAL 416391 P (Prop) R R/W REAL 416393 PW (Prop) W R INT 40104 I (Integral) R R/W REAL 416395 IW (Integral) W R INT 40105 OPMS R/W R/W DIGITAL 00039 DI1 (No Flow Sw) R R DIGITAL 00027 DI2 (spare) R R DIGITAL 00028 R1 (SV Crtl) MB1 R/W DIGITAL 00051 R2 (spare) MB2 R/W DIGITAL 00052 [MODBUS] InitType=1 Block=5 PollTime=150 timeout=8000 maxbits=1000 debugstr=* all FloatMode=1 |
Keywords: |
ABB Commander 351 |