Applies To: |
|
Summary: |
I have configured Process Analyst, in
CitectSCADA, and the alarm description for the Alarm Pens added in
process analyst show the Alarm Tag name of the first alarm tag in
the corresponding alarms entry, rather than the Configured alarm
description. e.g. If you add digital alarms, the alarm description will read the tag name of the first digital alarm tag. |
Solution: |
This is currently a limitation within
Citect, where in order to get the correct Alarm description, you
will be required to run Process Analyst on the CitectSCADA Alarm
Server.
A work-around is to use the Alarm comment instead of the Alarm
description. Process Analyst will then display the right
comment for every alarm. |
Keywords: |
Process Analyst, Alarm Description |