Applies To: |
|
Summary: |
I am using the latest S7NT driver and
getting a hardware error Generic 21 (Channel off-line, cannot talk)
Driver 20 or 0x14 (Channel not on-line). What is causing this
error? |
Solution: |
This can be caused by not setting the slot
number in the Siemens Netpro S7-Connection configuration, Address
details:
You must specify the slot number that the CPU is located in the PLC Rack. Normally for an S7-300 it is slot 2, and for a S7-400 it is slot 3. |
Keywords: |
S7NT, 0x14, Channel offline |