Applies To:
  • CitectSCADA 6.00
  • CitectHMI 6.00

When viewing the old-style trend pages on a v6.00 display client that is connected to a v5.50 trend server, some (or all) of the trend pens are not shown on the graph. 

This was caused by a change in the maximum trend tag name length (from 32 to 80) after v5.50. This has been fixed in CitectSCADA v6.10. A v6.10 trend display client should display all pens when connected to a v5.50 trend server. 

trend pen not shown display client