I am using the 1756 ControlLogix Ethernet module to connect CITECT to a PLC on a DH+ Network. How do I specify the addressing for this? |
Solution: |
We will use the following scenario, a SLC 5/04 with station address 1 is connected to a DH+ network. The 1756 ControlLogix DHRIO module channel A (Number 2) has been configured with a link ID of 20. This module is in slot 2 of the 1756 ControlLogix Chassis. The board type is ABRSLINX The port special option is the connection name in RSLINX (eg. TCP-1) The protocol is ABRSLINX500
|
Keywords: |
ABRSLINX, 1756 ControlLogix Ethernet, SLC, DH+, Addressing |