Applies To:
  • CitectSCADA 5.xx, 6.00
  • CitectHMI 5.xx, 6.00

Summary:
Cicode function Message() parameter mode would crash on invalid mode values.

Mode values of [0|1] + [16|32|48|64] are permitted to assert the behaviour of the
message box icon and OK|CANCEL button combination.

Some other mode values that do not equate to the above values can cause
Citect32.exe to crash. 
 

Solution:
Citect has confirmed this to be a problem in CitectHMI/SCADA versions 5.00 to 6.00.
This problem has been fixed in version 6.10.
 

Keywords:
Message() Cicode Mode  

Attachments