Applies To: |
|
Summary: |
Cicode function Message() parameter mode
would crash on invalid mode values. Mode values of [0|1] + [16|32|48|64] are permitted to assert the behaviour of the message box icon and OK|CANCEL button combination. Some other mode values that do not equate to the above values can cause Citect32.exe to crash. |
Solution: |
Citect has confirmed this to be a problem
in CitectHMI/SCADA versions 5.00 to 6.00. This problem has been fixed in version 6.10. |
Keywords: |
Message() Cicode Mode |
Related Links
Attachments