Applies To:
  • CitectSCADA 5.xx, 6.00
  • CitectHMI 5.xx, 6.00

Summary:
Projects that include the CSV_Include project may cause Citect/HMI SCADA IDC client and the CitectHMI/SCADA FTP Server to hang. The debug window on the FTP server will exhibit multiple client logins without corresponding logouts causing the FTP server to run out of resources and shutdown or hang.
 

Solution:
Citect has confirmed this to be a problem in CitectHMI/SCADA versions 5.XX to 6.00. This problem has been fixed in version (550C 600A)
 

Keywords:
IDC hang csv  