Summary:
Kernel startup messages are not saved where they can be retrieved easily.
 

Solution:
A new parameter has been added in the Citect.ini file:

[General]
VerboseToSyslog = 1

This will ensure all of the messages sent to the kernel debug window are logged in the syslog.dat file. This functionality is off by default.

This parameters will appear in CitectHMI/SCADA Version 6.10.
 

Keywords:
VerboseToSyslog Verbose syslog kernel startup  