ABCLX Status Tags of type BOOL turn the
unit offline regardless of the PLC point state (0 or 1) Where the Citect.ini declares a status tag as follows: [ABCLX] StatusTag=PLC_STATUS_TAG_BOOL=1 If point PLC_STATUS_TAG_BOOL is declared in the PLC as Type BOOL the ABCLX drivers 3.02.30.000 and below will not read the point value correctly and force the unit offline. |
Solution: |
Citect has confirmed this to be a problem
in CitectHMI/SCADA versions 6.XX of the ABCLX 3.02.30.000 version
of the driver. This problem has been fixed in version 3.02.30.001
and higher. |