Applies To:
  • CitectSCADA 6.00, 6.10
  • CitectHMI 6.00, 6.10

Summary:
ABCLX Status Tags of type BOOL turn the unit offline regardless of the PLC point state (0 or 1)

Where the Citect.ini declares a status tag as follows:

[ABCLX]
StatusTag=PLC_STATUS_TAG_BOOL=1

If point PLC_STATUS_TAG_BOOL is declared in the PLC as Type BOOL the ABCLX drivers 3.02.30.000 and below will not read the point value correctly and force the unit offline.
 

Solution:
Citect has confirmed this to be a problem in CitectHMI/SCADA versions 6.XX of the ABCLX 3.02.30.000 version of the driver. This problem has been fixed in version 3.02.30.001 and higher.
 

Keywords:
ABCLX Status Tag  