Applies To:
  • CitectSCADA 5.xx, 6.00, 6.10

MICRXNET Driver v1.00.06.000 B1 is not able to read BDw.b tags if all 32 bits are not declared to citect.

An error message in the syslog.dat file "Rejecting mismatched response" is reported. 

Citect has confirmed this to be a problem in MICRXNET versions up to and including v1.00.06.000 B1. This problem has been fixed in version

The driver has been modified to handle the sent byte count correctly for DWORD(32) data types like BDw.d.

The "Rejecting Mismatch Response" syslog.dat message has been enhanced to pinpoint the exact cause(s) of the response mismatch (it was not possible to easily resolve the root cause of the mismatch in previous versions of the trace logs).

MICRXNET Rejecting mismatched