Applies To:
  • CitectSCADA

Summary:
S7NT driver may crash at Citect shutdown if PLCs are offline. 

Solution:
 If the S7NT driver fails to bring any PLCs online, Citect may crash on shutdown.

The solution is to set these in the Citect.INI file

[ioserver]
alwayscallstopunit=1
alwayscallstopchannel=1

or use the S7NT driver from version v2.06.02.001 .

NB: Most API based drivers such as S7NT should use the above INI settings.