Applies To:
  • CitectSCADA 5.xx, 6.00

Summary:
Out of file handle error when compiling more than 110 include projects. 

Solution:
Citect has confirmed this is a limitation in CitectHMI/SCADA versions to v6.00. The limit has been increased to approximately 220 include project in version 6.10.

The previous limit was approximately 110 included projects.

The [ctedit]Dbfiles=x
Ranges have changed.

The maximum file count is now 510, the minimum 50, and the default 100. This value must be set to 510 if you need to compile up to 220 include projects.

Keywords:
 

Attachments