Applies To:
  • CitectSCADA 5.42, 5.42 Service Pack A, 5.50 Service Pack B, 5.50 Service Pack C, 6.XX
  • CitectHMI 5.42, 5.42 Service Pack A, 5.50 Service Pack B, 5.50 Service Pack C, 6.XX

Summary:
I cannot get the Bailey driver v2.1.00.243 and higher to communicate with CIU03 units even with the [BAILEY]CIU=1 citect.ini parameter set. These units return all 0s even when connected as a single unit with a single tag. The driver does not generate any errors. The Bailey driver v2.01.00.521 can communicate successfully to the CIU03 unit with the exact same project configuration and citect.ini parameters.
 

Solution:
You will need to set the following citect.ini parameters to allow communications

[BAILEY]
CIU=2
Options=27

This rectifies the startup initialisation error.

Page 2-6 Point 2 of the following document discusses this in more detail:

Bailey Product Instruction E93-905-9, "Enhanced Computer Interface Unit Programmer's Reference Manual", Bailey Controls, Wickliffe, Ohio 44092.
 