I cannot get the Bailey driver v2.1.00.243
and higher to communicate with CIU03 units even with the
[BAILEY]CIU=1 citect.ini parameter set. These units return all 0s
even when connected as a single unit with a single tag. The driver
does not generate any errors. The Bailey driver v2.01.00.521 can
communicate successfully to the CIU03 unit with the exact same
project configuration and citect.ini parameters. |
Solution: |
You will need to set the following
citect.ini parameters to allow communications [BAILEY] CIU=2 Options=27 This rectifies the startup initialisation error. Page 2-6 Point 2 of the following document discusses this in more detail: Bailey Product Instruction E93-905-9, "Enhanced Computer Interface Unit Programmer's Reference Manual", Bailey Controls, Wickliffe, Ohio 44092. |