Applies To:
  • CitectSCADA 5.xx, 6.xx
  • CitectHMI 5.xx, 6.xx

I have installed the CiKT driver to work with a PKTX / PKTXD card, and I am receiving error "0x22" when trying to communicate with my PLC via the ABTCP driver.

If you are using polled mode (set interrupt to 0 in Boards form) you should need to ensure you have set a poll time INI parameter.. For example:

PollTime = 10

This setting should resolve this issue.


PKTXD PKTX CiKT 22 0x22 board