Applies To: |
|
Summary: |
The Sentinel Protection Installer v7.2.1
installs a service called "Sentinel Protection Server". With this
service running the following issues can be experienced: 1. CitectSCADA server would "lock-up" after 8-24 hours of running normally. 2. CitectSCADA server would spontaneously reboot after 8-24 hours of running normally. The Sentinel Protection Server can create TCP and UDP sockets and destroy them in a very rapid manner (at least 1/sec). We believe that this can eventually cause a TCP/IP stack or memory problem. |
Solution: |
Disable the "Sentinel Protection Server"
service by manually stopping it and setting the startup type to
"Manual". |
Keywords: |
Sentinel, Protection, Key |
Related Links
Attachments