Applies To: |
|
Summary: |
Problem: I have configured Citect as an OPC
client and using Matrikon OPC simulation as a server. Matrikon OPC
server is running on a remote PC. During runtime, the tags show
#COMS and I encounter the following error screens.
Access Violation Error
PLC Data not yet Valid Hardware Alarm
|
Solution: |
In the boards form, enter the computer
name where Matrikon OPC server is installed. Compile and run the
project again.
|
Keywords: |
OPC, Citect OPC client, Matrikon OPC server, PLC Server Data Not yet Valid ,Access Violation Error |
Related Links
Attachments