Applies To: |
|
Summary: |
I cannot seem to get OPC Status tags
working when the condition is anything but the default
"ISGOOD" |
Solution: |
It is a little confusing to configure
this. You need to ensure that the parameter is entered correctly
with an "=" before the value of the parameter. This seems strange
because the condition values also contain = For example to set a condition of equal to 1 you need to enter Default.Condition==1 or if you want the condition to be >=100 you would need to enter Default.Condition=>=100 |
Keywords: |
Related Links