Is there a Citect driver available for GE
Fanuc Rx3i PLC’s that supports symbolic addressing (aka "Tag based"
addressing). |
Solution: |
There is no native CitectSCADA driver to
support the Rx3i symbolic addressing and the GETCP driver using the
numerical / register addressing is the current method (this does
however require the latest version of the GETCP driver, refer to
Q4255). If this functionality is important
to your project you can use an OPC server together with
CitectSCADA's OPC client driver. GE Fanuc provide an OPC server free of charge * http://globalcare.gefanuc.com/downloads/drivers/showdrivers.asp?objid=889 There are also numerous 3rd party OPC servers which support this. eg Kepware * http://www.kepware.com/Spec_Sheets/GE_Ethernet.html Requests for a native CitectSCADA driver will be monitored and any future decisions will be based on customer demand. |