When TrnSetTable() is called, the data is
only written to the server that the client is connected to. The
redundant server does not receive the data. This happens if I pass
in a period parameter that does not match the actual trend tag
period. If I pass in the actual trend tag period instead, or 0
(which uses the actual trend tag period), there is no issue. |
Solution: |
Citect has confirmed this to be a problem
in CitectHMI/SCADA versions v5.5x. This problem has been fixed in
version v6 and higher. |
Keywords: |
trnsettable, redundant, trend, backfill |