TrnSetTable() does not write to the correct
sample period when the data period passed in does not match the
actual trend period. That is, if you pass in a value for the period
parameter of TrnSetTable() which does not match the sample period
defined in the trend tag database. |
Solution: |
This problem does not apply if you pass in
the actual sample period of the trend tag as the Period parameter
of TrnSetTable(), or use the value 0 (which uses the trend tag
sample period). Citect has confirmed this to be a problem in CitectHMI/SCADA versions v6 to v6.1a. We are researching this problem and will post new information here as it becomes available. |