Applies To: |
|
Summary: |
CitectSCADA (as an OPC Server) and
Wonderware OPCLink (as an OPC Client) used to work via DCOM on two
separate machines using Program ID 'Citect.OPC'. Now when
CitectSCADA and OPC Link are on the same machine (not using DCOM)
and using Program ID 'Citect.OPC'... OPC Link cannot connect and
hence does not get data from CitectSCADA. |
Solution: |
Use Program ID 'Citect.OPCRemote' instead
of 'Citect.OPC' when CitectSCADA and Wonderware OPCLink are on the
same machine not using DCOM. |