Applies To:
  • CitectSCADA X.XX
  • CitectHMI X.XX

I have a Hardware Alarm that I would like to exclude from being displayed on the Hardware Alarms page. 

Place the following parameter in your Citect.ini file:

HwExclude = 0x0000

Where 0x0000 corresponds to the value displayed in the Error field in the HardAlm.DBF. HardAlm.DBF is located in the CitectSCADA\User\System folder. The Error field will correspond to the desired Hardware alarm description that is to be excluded.


[Alarm] HwExclude Exclude Hardware Alarm Alarms Exclusion