Applies To: |
|
Summary: |
In a redundant, pure TCP/IP network (where
NetBIOS is disabled on both Servers), the following DNS parameters
have been defined on the Primary and Standby Servers: [DNS] Primary=xxx.xxx.13.25 Standby=xxx.xxx.13.48 In runtime, when an alarm have been triggered on and off, acknowledging the alarm on the Primary server will work but the alarm will not get acknowledged on the Standby server. Similarly when acknowledging alarms on a standby server they are not seen as acknowledged on the Primary server. |
Solution: |
The alarm will display as acknowledged on
both Servers when you use the extended DNS parameter to specify
your servers as shown below. Adding the following DNS parameters to both INI files worked around this issue. [DNS] IOServerP=xxx.xxx.13.25 IOServerS=xxx.xxx.13.48 CitectPAlarm=xxx.xxx.13.25 CitectSAlarm=xxx.xxx.13.48 CitectPReport=xxx.xxx.13.25 CitectSReport=xxx.xxx.13.48 CitectPTrend=xxx.xxx.13.25 CitectSTrend=xxx.xxx.13.48 The names above can be verified against the INI files on the
Primary and Standby servers: |
Keywords: |
Alarms, Acknowledge, Redundancy, TCPIP |
Related Links
Attachments