Applies To: |
|
Summary: |
ABRSLINX returning BAD DATA errors (32) when reading BCD data types |
Solution: |
From build V1.02.09.001 a check was made
for valid BCD values. However it is possible with blocking for non-BCD registers to be read. A new build has been made (V1.02.13.000) with a new Citect.INI parameter to enable this check [ABRSLINX]BCDCheckEnable=1 The default value is 0 - No check |
Keywords: |
ABRSLINX DCB |
Related Links