Applies To: |
|
Summary: |
The Multi-Digital alarms State Description field {State_Desc,n} does not get updated on the Alarm Page when the alarm changes state. |
Solution: |
Set the Realarm field to 1. A value of 1 in this field causes a new Time and State Description {State_Desc,n} to be recorded when the states change. With a value of 0, only the Time and State Description {State_Desc,n} of the first alarm state is recorded on the Alarm Pages. |
Keywords: |
MultiDigital Alarms State_Desc realarm |
Related Links