Applies To:
  • CitectSCADA 6.xx
  • CitectHMI 6.xx

We use multi-language support and have updated the pglang.dbf in our include project.
If we do a page update from the Graphics Builder and then pack or compile the main project in Project Editor we get the following error:

"...\pglang.dbf "Error Opening file:"


The problem was the result of the main project's pglang,dbf file having the first column (header "NATIVE") size of 254 characters.  This should have been 100 characters as specified in the citect.frm file and as used in your modified Include project's pglang.dbf file.

New projects are created with field size of 100, as does the CSV_Include project, however the Include and System projects have used 254 characters.

Citect has confirmed this to be a problem in CitectHMI/SCADA version 6.XX. We are researching this problem and will post new information here as it becomes available.