Applies To: |
|
Summary: |
Since
upgrading Premium firmware from PL7 to Unity, error 0x105 is
observed when reading and writing to the following
registers: %I, %IW, %Q, %QW. Details of
Driver error: |
Solution: |
Substantial changes have been made to the
Unity firmware. This includes a rationalisation of the Uni-TE
requests supported by the Premium Unity processors. Currently the only registers supported by the Premium Unity processors are: Read internal - %M Read internal word - %MW Write internal bit - %M Write internal word - %MW It is highly recommended that users wanting to communicate with the Premium Unity processors use either the Modnet protocol, or OPC protocol. For more
information about which Uni-TE requests the Premium Unity
processors support, please consult the Schneider FAQ
entitled: |
Keywords: |
Related Links
Attachments