I have a CitectSCADA project that is
configured to communicate to Unitronics controllers (Vision 230
with Ethernet card), using the modnet protocol. The device seems to
go offline if CitectSCADA does not read from it for 5 seconds. Why
is this happening? |
Solution: |
The Unitronics controllers (Vision 230
with Ethernet card) has a TCP timeout, and the value by default is
set to 5 seconds. This means that if there is no activity between
the device and CitectSCADA for 5 seconds, the device will drop the
connection.
The TCP timeout setting for the Unitronics controller needs to
be increased to a reasonable value to prevent the device from
dropping of the connection for brief periods of
inactivity. |
Keywords: |
Unitronics controllers, Vision 230, Modnet, #COM |