Applies To:
  • CitectSCADA 6.xx
  • CitectHMI 6.xx

Summary:
AlarmGetDsp ‘type’ displays an undocumented condition ‘CLEARED’

Alarm documentation:

{Type,n} The type of alarm or condition:
DISABLED
ACKNOWLEDGED
UNACKNOWLEDGED

Cicode Function:

STRING sType = AlarmGetDsp(AN, "Type");

‘Alarm Information’ displayed:


 

Solution:
Alarms will go into a CLEARED state when the AlarmClear() cicode function is called on alarms that are acknowledged and off.  

Keywords:
AlarmGetDsp category information type cicode alarm  