Applies To:
  • CitectSCADA 6.0, 6.1, 6.1A
  • CitectHMI 6.0, 6.1, 6.1A

Summary:
Graphics Builder automation Projectpackdatabase() function doesnt work.  

In V6.X, calling the automation function ProjectPackDatabase returns error 0x80010105 ("The server threw an exception"). However, the pack called from Project Editor works.

Solution:

When you try to call the ProjectPackDatabase() function it throws an exception (0x80010105). This is often (but not always) accompanied by the error message "Error:C:\Documents and settings\All Users\Application Data\CitectSCADA\User\Master.DBF Invalid File Name".CIT has confirmed this to be a problem in Citect for Windows version 6.x. This issue has been fixed 6.1SPKB.

 

Keywords:
 

Attachments