Applies To:
  • CitectSCADA 7.xx
  • CitectHMI 7.xx

Summary:

After upgrading my projects to CitectSCADA Version 7 and redeploying the project, my Web Client no longer works.  


Solution:

One possibility is that the Web Client temporary files need to be deleted. These are different to temporary internet files and can be found at C:\Document and Settings\<Current user logon>\Local Settings\Temp\Citect

A difference in setup between Version 6 and Version 7 may cause issues.

In Version 6, the IIS Default Web Site name is 'CitectSCADA' and the user browses to www.<servername>.com/CitectSCADA

In Version 7, the IIS Default Web Site name is 'Citect', therefore the user will need to browse to www.<servername>.com/Citect

 

Keywords:
 

Attachments